Lightning strikes cannot be prevented, however a system can be installed that will prevent damage or at least reduce damage.
A well-bonded vessel is more resistant to the effects of a nearby or direct strike. Vessels with bonding systems, even partial, in poor repair or otherwise but with relatively good bonding cables to exposed metal, through-hulls, keel and the seawater, suffer less damage than those with no bonding system. The primary goal is some level of safety and protection to crew. Secondarily, to prevent damage to gear, electronics etc. While a good bonding and shore-power ground systems reduce the damage, a dedicated system is preferred.
A lightning rod/conductor should be made from solid 9mm copper, or 13mm aluminium rod (better suited to aluminium masts), the top should be domed and above essentially everything. It is connected by a heavy gauge wire 21mm square. Secondary cables 6mm square can be attached to exposed ballast keel, shafts, struts, and rudders but need to be more or less directly below the lightning rod. The lightning plate under the hull, for maximum effectiveness, the edges to be square, or sharp, and not filleted with caulk or fairing. It is the edges that do the strike dissipation, so the longer the better.
Preference is for 6mm thick, 2.5 – 5cm wide copper strip parallel with the vessel’s centreline. Through bolts connect this to the hull, and serve as connection points for the primary conductor, as well as for secondary conductors from other bonded gear and underwater metals.